Hazardous-area lighting guide

Explosion-proof lighting: zones, Ex marking, how to select and how to use

Choosing a light for a hazardous area is not about brightness first - it is about the zone, the gas or dust, and the temperature. This guide explains each part of the ATEX / IECEx marking in plain words, how to match a light to your site and job, and how to use and look after it safely.

The basics: why a normal light is dangerous

An explosion needs three things at the same time: a flammable gas, vapour or dust, oxygen (air) and an ignition source. In refineries, petrochemical plants, tank farms, fuel stations, paint shops and grain or powder handling, the first two are often present. A normal torch or lamp can become the third - through a spark from the switch or battery contacts, an electrical fault, or a hot surface.

Explosion-proof (Ex) lighting is designed and certified so that it cannot ignite the surrounding atmosphere: it either keeps the energy too low to ignite anything, contains any internal explosion inside a strong housing, or keeps sparks and hot surfaces away from the gas.

ATEX

The European legal framework for equipment in explosive atmospheres (Directive 2014/34/EU). Marked with the Ex hexagon and the equipment group and category, for example II 1G.

IECEx

The international certification scheme based on the IEC 60079 standards. Uses the same zones, gas groups and temperature classes, with an IECEx certificate number.

What your site asks for

Most projects in Saudi Arabia name ATEX and / or IECEx in the specification. Always follow the area classification drawing and the client or site specification.

Hazardous-area zones

Sites are divided into zones according to how often an explosive atmosphere is present (IEC 60079-10-1 for gas, IEC 60079-10-2 for dust). The zone is set by the site's area classification - it is not chosen by the user of the light.

ZoneExplosive atmosphere is present...Typical examplesEquipment needed
Zone 0 (gas)continuously or for long periodsinside storage tanks and process vessels above the liquid, inside pits and sumpsCategory 1G / EPL Ga
Zone 1 (gas)likely in normal operation, from time to timearound vents, filling and sampling points, pump seals, loading baysCategory 2G / EPL Gb (or 1G)
Zone 2 (gas)not likely in normal operation, and only for a short timeareas around Zone 1, flanges and valves that leak only on failureCategory 3G / EPL Gc (or 1G, 2G)
Zone 20 (dust)continuously as a dust cloudinside silos, hoppers, mills, dust collectorsCategory 1D / EPL Da
Zone 21 (dust)likely in normal operationaround filling and emptying points, bag tippingCategory 2D / EPL Db (or 1D)
Zone 22 (dust)not likely, and only for a short timenear dust-handling equipment where layers can be disturbedCategory 3D / EPL Dc (or 1D, 2D)
Rule of thumb: a light certified for a higher-risk zone can always be used in a lower-risk zone (a Zone 0 torch is fine in Zone 1 and 2) - never the other way round. Gas and dust are separate: a light rated only for gas (G) is not automatically rated for dust (D).

Reading the Ex marking - an example

Every certified light carries a marking on its label. Here is a typical marking for a light that may be used in Zone 0, explained part by part (example for illustration - always read the label of the actual product):

〈Ex〉 II 1GEx iaIICT4Ga
PartMeaning
〈Ex〉The ATEX explosion-protection symbol.
IIEquipment group II: surface industries (group I is for underground mines).
1GCategory 1 for gas: suitable for Zone 0, 1 and 2. 2G = Zone 1 and 2, 3G = Zone 2 only. "D" instead of "G" means dust.
Ex iaThe type of protection - here intrinsic safety, level "a" (the highest). See the protection types below.
IICGas group - IIC covers the most easily ignited gases (hydrogen, acetylene) and also IIB and IIA.
T4Temperature class - the surface will not exceed 135 °C.
GaEquipment Protection Level (EPL) - Ga = very high protection for gas, suitable for Zone 0.

The label also shows the certificate number (ATEX and / or IECEx), the ambient temperature range (for example -20 °C to +40 °C) and the IP rating. In hot Saudi summers, check the maximum ambient temperature on the label against the conditions where the light will be used and stored.

Gas groups and temperature classes

Gas groups

GroupTypical gasesLight rated ... can be used
IIApropane, methane (surface), butane, petrol vapourIIA, IIB or IIC
IIBethylene, hydrogen sulphide, town gasIIB or IIC
IIChydrogen, acetylene, carbon disulphideIIC only

Temperature classes

ClassMax. surface temperature
T1450 °C
T2300 °C
T3200 °C
T4135 °C
T5100 °C
T685 °C
The temperature class must be below the auto-ignition temperature of every gas that can be present. A T4 light (135 °C) is suitable for any gas that ignites above 135 °C; a T6 light covers more gases. For dust, the label shows a maximum surface temperature in °C (for example T135 °C) that must stay below the ignition temperature of the dust cloud and dust layer.

Types of protection you will see on lights

CodeNameHow it protectsCommon on
Ex ia / ib / icIntrinsic safetyElectrical energy is kept too low to ignite gas, even with faults. "ia" is the highest level (Zone 0).torches, headtorches, handlamps
Ex d / dbFlameproof enclosureA strong housing contains any internal explosion and cools escaping gases.floodlights, installed fittings
Ex e / ebIncreased safetyExtra measures prevent sparks and hot spots in normal use.terminal boxes, linear fittings
Ex m / mbEncapsulationSpark-producing parts are sealed in compound.LED modules, electronics
Ex op isInherently safe optical radiationThe light output itself cannot ignite the atmosphere.LED light sources
Ex t / tbProtection by enclosure (dust)The housing keeps dust out and limits surface temperature.lights for dust zones

How to select the right explosion-proof light - 6 steps

  1. Find the zone. Check the area classification drawing or ask the area authority / HSE. If the light will move between areas (for example a torch carried on rounds), choose for the highest-risk zone it will enter.
  2. Find the gas group (or dust) and temperature class. The site data sheet or the permit gives the substances. Choose a light with the same or a higher gas group (IIC covers all) and a temperature class below the auto-ignition temperature.
  3. Define the job. Walking and checking (torch), hands-free work (headtorch), close inspection (handlamp), lighting a work area (floodlight), lighting inside a tank or vessel, permanent lighting, or emergency lighting.
  4. Choose the power. Replaceable batteries are simple and need no charger on site; rechargeable lights save battery cost on daily use; mains or low-voltage (for example 24 V via a transformer) lights suit long shutdown work. Inside tanks and vessels many sites specify low-voltage supply.
  5. Check the details. Light output and run time for the shift, beam (spot or flood), weight, IP rating, ambient temperature range, mounting (helmet, magnet, tripod, hook) and the certificate your client accepts (ATEX, IECEx or both).
  6. Plan the accessories. Chargers and charger banks, spare battery packs, helmet brackets, stands, cable reels, transformers and splitter boxes - and where they will be used (most chargers belong in a safe area).

How to use explosion-proof lights safely

Do

  • Read the label and the manual before first use - zone, gas group, temperature class and ambient range.
  • Check the light before every shift: housing, lens, seals, switch, battery cover and cable undamaged.
  • Change batteries and charge in a safe area, unless the manual and certificate allow otherwise.
  • Use only the battery types and chargers named by the manufacturer.
  • Keep the light clean - thick dust layers raise the surface temperature.
  • For tanks and vessels, follow the confined-space permit and gas test; place transformers and supply points outside the space.
  • Label and remove from service any light that is damaged, and record it.

Do not

  • Open the light, change batteries or bulbs/modules inside the hazardous area.
  • Mix old and new batteries, or use a different battery type or brand than specified.
  • Take a Zone 2 light into Zone 1 or Zone 0, or a gas-only light into a dust zone.
  • Use a light with a cracked lens, missing screws or a damaged seal.
  • Repair or modify certified equipment yourself - this voids the certification.
  • Leave lights in direct sun above the label's maximum ambient temperature.
  • Treat "ATEX" alone as enough - the group, category and T-class must match the site.

Inspection and maintenance

Ex equipment must be inspected so it stays safe through its life. The IEC 60079-17 standard describes three grades of inspection: visual (defects you can see without tools), close (visual plus checks such as loose fixings, with access equipment if needed) and detailed (opening the equipment where allowed, by a competent person).

For portable lights a simple routine works well: a pre-use check by the user every shift, a periodic inspection by the store or maintenance team with a record against each light's serial number, and repair only by the manufacturer or an authorised workshop. Keep the certificate and manual with the records - site auditors often ask for them.

Find the right light

Answer three questions and see the matching explosion-proof lights and equipment. Zone badges come from each product's published data; where a rating is not listed, ask us for the certificate.

Not sure which explosion-proof product you need?

Tell us where and how you will use it – we show the right certified lights and equipment. New to explosion-proof equipment? Read the guide →

Frequently asked questions

Can a Zone 0 light be used in Zone 1 or Zone 2?

Yes. Equipment certified for a higher-risk zone may be used in the lower-risk zones: category 1G / EPL Ga equipment can be used in Zone 0, 1 and 2. The reverse is not allowed.

What does IIC mean on an ATEX light?

It is the gas group. IIA covers gases such as propane, IIB gases such as ethylene, and IIC the most easily ignited gases such as hydrogen and acetylene. A IIC light is also suitable for IIB and IIA.

What does T4 mean?

The surface of the equipment will not exceed 135 °C. The temperature class must be lower than the auto-ignition temperature of the gas present; T6 (85 °C) is the strictest.

Can I charge or change batteries inside the hazardous area?

Only if the product instructions and its certificate allow it. For most portable lights, batteries are changed and chargers are used in a safe area, with only the battery types named in the manual.

Is ATEX the same as IECEx?

Both use the IEC 60079 standards and the same zone and marking logic. ATEX is the European legal framework, IECEx the international certification scheme. Check which one your site or client specification requires.

Is "explosion-proof" the same as "intrinsically safe"?

Not exactly. "Explosion-proof" is often used for any Ex-certified equipment, while in IEC terms it usually means a flameproof enclosure (Ex d). Intrinsic safety (Ex i) is a different method that limits energy. Both can be correct for a zone - the marking tells you which method is used.

Need help choosing?

Send us the zone, gas group, temperature class and the job, and we will recommend the right light and accessories.

Ask West Velocity →

This guide gives general information. The area classification, permit and the product's certificate and manual always take priority.