ePROX Inductive Proximity Sensor M18 Non-Shielded
ePROX M18 non-shielded inductive proximity sensor from BCH Electric Limited for non-contact detection of metal objects in plant automation. Nominal sensing distance 8 mm. 3-wire DC (PNP/NPN) or 2-wire AC output, 12-30V DC; 240V AC / 110V AC, IP 67, LED status indication, with reverse-polarity, short-circuit, false-pulse and transient-noise protection. Housing: Nickel Plated Brass.
Specifications
| Nominal Sensing Distance (Sn) | 8 mm |
| Sn Tolerance | ± 10% |
| Operating Frequency | 500 Hz (DC); 15 Hz (AC) |
| Supply Voltage | 12-30V DC; 240V AC / 110V AC |
| Hysteresis | ≤ 10% |
| Repeatability | ≤ 2% |
| Max. Output Current | 200 mA |
| Output Indication | LED |
| Leakage Current (Load) | Max. 10 µA (DC) |
| Operating Temperature | 0 to +55°C |
| Protection Degree | IP 67 |
| Reverse Polarity | Provided |
| Short Circuit | Provided |
| False Pulse | Provided |
| Transient Noise | Provided |
| Housing | Nickel Plated Brass |
| Marks | CE |
| Output (NO/NC) | 3 Wire DC; 2 Wire AC |
Ordering & Options
Ordering options (select when ordering): output type — PNP / NPN / DC 2-Wire / 220V AC / 110V AC (Namur on request); output configuration — NO / NC / 1NO+1NC (1NO+1NC not available on 2-wire DC/AC); connection — prewired 2 m cable, connector (K) or short length 45 mm (S). Applicable standards: IS-13947, EN-61000-3-3 & EN-61000-3-4, CSA-22.2 No. 14-95. Utilisation category DC-13 per IEC 60947-5-2.